4.2.5 Jumper Settings
Jumper settings are applied to functions such as main-disconnect time, Start function, system
information (serial number/ID code) programming, and system testing. Jumpers #1 - #7 are
located on the decoder/relay board between the receiving RF module and the output relays
(refer to Fig.16 below).
(Fig. 16)
Manufacture preset
Jumper Settings Function
JP1
(Blank)
JP2
(Blank)
Receiver MAIN remained closed until the transmitter power is turned
off or emergency stop command is initiated.
JP1
(Inserted)
JP2
(Blank)
Receiver MAIN opens after 5 minutes of system inactivity.
JP1
(Blank)
JP2
(Inserted)
Receiver MAIN opens after 30 minutes of system inactivity.
JP1
(Inserted)
JP2
(Inserted)
Receiver MAIN opens after 60 minutes of system inactivity.
JP3
(Blank)
Press any push button on the transmitter to activate the receiver MAIN at
system startup, after e-stop reset, and after system inactivity
(refer to JP1 & JP2 settings above).
JP3
(Inserted)
Rotate the power key switch to “START” position to activate the receiver
MAIN at system startup, after e-stop reset, and after system inactivity
(refer to JP1 & JP2 settings above).
JP6
(Blank)
Program system serial number/ID code and channel from decoder module
to I-CHIP.
JP6
(Inserted)
Program system serial number/ID code and channel from I-CHIP
to decoder module.
JP7
(Inserted)
For system test only, receiver MAIN disabled.